Electrical / transformer room 12.0 × 6.0 m at ground level on the north boundary, reached from the service road.

✓ CompliedRC presentation REV09 · p. 15, 130

Answer

Electrical / transformer room: 12.00 m x 6.00 m = 72 m2, at ground level on the north boundary of Lot 26, between the landscaping strip and the hotel parking bays 13-24, beside the back office (R10 ground floor plan). Direct access from the parking aisle and the service road for RCJY / utility vehicles and transformer replacement, away from guest areas.

Equipment (BOQ 14.H.11): MV ring main unit (13.8 kV), oil-free cast-resin transformers 13.8 kV / 400-230 V, LV main switchboard feeding the basement and floor distribution; standby generators N+1 (location by MEP).

Preliminary demand about 3.5-4.0 MVA (about 100 W/m2 x 36,100 m2 GFA) - transformer number and rating, ventilation and fire rating (2-hour enclosure) to be confirmed by the MEP engineer and the RCJY utilities department.

Key data and sources

Each figure with the drawing, study or standard it comes from.

ItemValueSource
Transformer room size12.00 x 6.00 m = 72 m2R10 ground floor plan
LocationGround level, north boundary Lot 26, beside parking bays 13-24 and back officeR10 ground floor plan
AccessFrom parking aisle / service road, for utility vehicles and replacementR10
EquipmentMV RMU 13.8 kV, cast-resin transformers 13.8 kV / 400-230 V, LV main switchboardBOQ 14.H.11
Demandabout 3.5-4.0 MVA (about 100 W/m2 x 36,100 m2)Prelim. - MEP to confirm
Room rating2-hour fire-rated enclosure, mechanical ventilationSBC 801 / Prelim. - MEP to confirm
StandbyGenerators N+1, location by MEPBOQ 14.H.11

Drawing evidence – R17 sheets

The latest issued drawings (8 November 2026). Click a sheet to open it full size.

WFY-AR-100
WFY-AR-100Site development and landscape plan
WFY-AR-102
WFY-AR-102Ground floor plan – hotel

Where it is in the RC presentation

Wafaiya_Yanbu_RC_Submission_REV09.pdf (135 pages) – click a page to open it full size.

Presentation page 15
Page 15
Presentation page 130
Page 130

Evidence photos

The photos attached to this item in the compliance answer sheet.

Evidence photo 1
Photo 1
Evidence photo 2
Photo 2

References

  • R10 Architectural Plans Y5S-AR-GF-01 (electrical room 12.00 x 6.00 m); BOQ 14.H.11; RCJY utilities